Features| Model | ULT-P30K(L)33 | ULT-P40KL33 | ULT-P60KL33 | ULT-P80KL33 | |
| Phase | 3 Phase input / 3 Phase output | ||||
| Capacity | 30KVA / 27KW | 40KVA / 36KW | 60KVA / 54KW | 80KVA / 72KW | |
| Input | |||||
| Nominal Voltage | 3 x 380/400/415 Vac (3Ph+N) | ||||
| Voltage Range | 190 ~ 520 VAC (3-Phase) @ 50% Load; 305 ~ 478 VAC (3-Phase) @ 100% Load | ||||
| Frequency Range | 46~54Hz or 56~64Hz | ||||
| Power Factor | ≥0.99 @ 100% load | ||||
| THDi | ≤ 5% @100 ~ 130 VAC or 205 ~ 245VAC @ input THDU < 1.6% and full linear load condition with battery fully charged | ||||
| Output | |||||
| Output Voltage (Pure Sine Wave) | 3 x 360/380/4000/415Vac (3Ph+N) | ||||
| AC Voltage Regulation (Batt. Mode) | ±1% | ||||
| Frequency Range (Batt. Mode) | 50 Hz ±0.1 Hz or 60 Hz ±0.1 Hz | ||||
| Current Crest Ratio | 3:1 | ||||
| Harmonic Distortion | ≤2% THD (linear load); ≤5% THD (non-linear load) | ||||
| Transfer Time | Zero @ AC Mode <=> Batt. mode & Inverter <=> bypass | ||||
| Overload | AC Mode | 100 ~ 110% for 10 min, 110 ~ 130% for 1 min, > 130% for 1 second | |||
| Battery Mode | 100 ~ 110% for 30 seconds, 110 ~ 130% for 10 seconds, > 130% for 1 second | ||||
| Efficiency | |||||
| AC Mode | 95% | ||||
| Eco Mode | 98% | ||||
| Battery Mode | 92% | ||||
| Battery | |||||
| Standard Model | Battery Type | 12V / 7AH | 12V / 9AH | N/A | |
| Numbers | (2 x 16) pcs x 2 strings | (2 x 16) pcs x 2 strings | |||
| Typical Recharge Time | 9 hours recover to 90% capacity | ||||
| Charging Current (max.) | 2A | 
||||
| Charging Voltage | ±218.4 VDC (13.65 VDC x 32 pcs) | ||||
| Long-run Model | Battery Type | Depending on the capacity of external batteries | |||
| Numbers | 2 x (16 ~ 20) pcs (Adjustable) | ||||
| Charging Current (max.) | 4A | 8A | |||
| Charging Voltage | ±13.65 V x N (N=16 ~ 20) | ||||
| Indicators | |||||
| LCD Display | UPS status, load level, battery level, input/output voltage, discharge timer, and fault  | 
||||
| Management | |||||
| Smart RS-232 / USB | Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux/Unix/MAC | ||||
| Optional SNMP | Power management from SNMP manager and web browser | ||||
| Physical | |||||
| Standard Model | Dimensions (DxWxH) (mm/in) | 
 815x300x1000 / 32.1x11.8x39.4  | 
 N/A  | 
||
| Net Weight (kg/lb) | 
 205/451.5  | 
 230/506.6  | 
|||
| Long Run Model | Dimensions (DxWxH) (mm/in) | 
 592x250x576 / 23.3x9.8x22.7  | 
 790x360x900 / 31.1x14.2x35.4  | 
||
| Net Weight (kg/lb) | 
 43/94.8  | 
 45/99.2  | 
 95/209.5  | 
||
| Model | ULT-P100KL33 | ULT-P120KL33 | ULT-P160KL33 | ULT-P200KL33 | |
| Phase | 3 Phase input / 3 Phase output | ||||
| Capacity | 100KVA / 90KW | 120KVA / 108KW | 160KVA / 144KW | 200KVA / 180KW | |
| Input | |||||
| Nominal Voltage | 3 x 380/400/415 Vac (3Ph+N) | ||||
| Voltage Range | 190 ~ 520 VAC (3-Phase) @ 50% Load; 305 ~ 478 VAC (3-Phase) @ 100% Load | ||||
| Frequency Range | 46~54Hz or 56~64Hz | ||||
| Power Factor | ≥0.99 @ 100% load | ||||
| THDi | ≤ 5% @100 ~ 130 VAC or 205 ~ 245VAC @ input THDU < 1.6% and full linear load condition with battery fully charged | ||||
| Output | |||||
| Output Voltage (Pure Sine Wave) | 3 x 360/380/4000/415Vac (3Ph+N) | ||||
| AC Voltage Regulation (Batt. Mode) | ±1% | ||||
| Frequency Range (Batt. Mode) | 50 Hz ±0.1 Hz or 60 Hz ±0.1 Hz | ||||
| Current Crest Ratio | 3:1 | ||||
| Harmonic Distortion | ≤2% THD (linear load); ≤5% THD (non-linear load) | ||||
| Transfer Time | Zero @ AC Mode <=> Batt. mode & Inverter <=> bypass | ||||
| Overload | AC Mode | 100 ~ 110% for 10 min, 110 ~ 130% for 1 min, > 130% for 1 second | |||
| Battery Mode | 100 ~ 110% for 30 seconds, 110 ~ 130% for 10 seconds, > 130% for 1 second | ||||
| Efficiency | |||||
| AC Mode | 95% | ||||
| Eco Mode | 98% | ||||
| Battery Mode | 92% | 93% | |||
| Battery | |||||
| Standard Model | Battery Type | N/A | |||
| Numbers | |||||
| Typical Recharge Time | |||||
| Charging Current (max.) | |||||
| Charging Voltage | |||||
| Long-run Model | Battery Type | Depending on the capacity of external batteries | |||
| Numbers | 2 x (16 ~ 20) pcs (Adjustable) | ||||
| Charging Current (max.) | 12A | 16A | |||
| Charging Voltage | ±13.65 V x N (N=16 ~ 20) | ||||
| Indicators | |||||
| LCD Display | UPS status, load level, battery level, input/output voltage, discharge timer, and fault  | 
||||
| Management | |||||
| Smart RS-232 / USB | Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux/Unix/MAC | ||||
| Optional SNMP | Power management from SNMP manager and web browser | ||||
| Physical | |||||
| Standard Model | Dimensions (DxWxH) (mm/in) | N/A | |||
| Net Weight (kg/lb) | N/A | ||||
| Long Run Model | Dimensions (DxWxH) (mm/in) | 
 850x550x1500 / 33.5x21.7x59.1  | 
 950x550x1700 / 37.4x21.7x66.9  | 
 1000x650x2100 / 39.4x25.6x82.7  | 
|
| Net Weight (kg/lb) | 
 150/330.8  | 
 185/407.9  | 
 250/551.3  | 
||
10, El Mosheer Ahmed Ismail Str., Sidi Gaber
 Alexandria,
 Egypt
Call Us: +203 541.0172